Are you getting an error when trying to import ETS6/6.1 projects into Niagara?
The knxnetIp module, which is by default added to the Niagara 4.12, is incompatible with the ETS6/ETS6.1 projects. Below is an article on remedying this.
To solve the problem, follow the below steps:
-
Download the newest Tridium_EMEA_N4_Driver_Pack-4.12.X.Y.zip file from the https://support.innon.com archive, Software group https://support.innon.com/Tridium%20Niagara/Niagara4/Drivers/Driver_Pack/
-
Set the option of reading new KNX file versions to true;

-
Save the KNX project from ETS6/ETS6.1 in ETS5 and import the ETS5 project to the controller;
-
For ETS6/ETS6.1 projects it is possible to install the knxnetIp module in version 4.10.9.8 or higher 4.10 version.